Presolicitation · 36C25026B0046
J047--FY26 NRM -Medical Gas Deficiency 610A4-26-507 (VA-26-00058207)
SCOPE A recent medical gas evaluation identified deficiencies on the 3rd Floor. The Contractor shall correct all cited items and ensure all O (OXYGEN), MA (COMPRESS MEDICAL AIR), VAC (MEDICAL VACUUM), WAGD (Waste Anesthetic Gas Disposal), N (Nitrogen), N O (Nitrous Oxide), valves, alarms, and infrastructure are fully code compliant and fully operational. Code Compliance Requirements All work shall be performed in accordance with NFPA 99, 2018 Edition. Any location where N O or halogenated anesthetic agents may be administered - including CT, X-ray, and imaging rooms using roll in anesthesia machines - shall be equipped with dedicated WAGD inlets. Rooms receiving WAGD shall be treated as anesthetizing locations. Contractor shall provide: A dedicated zone valve assembly per NFPA 99 Section 5.1.4.6.2. Area alarm coverage meeting NFPA 99 requirements. INFECTION CONTROL RISK ASSESSMENT (ICRA) Contractor shall coordinate with Infection Prevention and Control and complete an ICRA before work…
Excerpt as published. The complete description, attachments, and any amendments are on the official notice.